European HVAC & AC spare-parts marketplace
Free planning tool · Sources documented

Air conditioner size & summer running-cost calculator

Size a single-room air conditioner and estimate May–September electricity cost using hourly European weather data (PVGIS 5.3) and an open heat-balance model.

Room & usage inputs

1. Where

Berlin, DE · 1% summer peak 30.6 °C

Loaded from our own server — no geolocation or external requests.
2. Room
Floor position
Window size
Main window direction
Building weight
3. Use
Extra heat sources
Default: 37.97 ct/kWh (Germany H1 2026 average, Destatis).
AC type

Recommended size & running cost

Recommended unit size2.0 kW6,824 BTU/h

Peak load 1.7 kW (including cool-down after switch-on) — rounded up to the next standard 2.0 kW unit.

Calculated for one room. A certified installer confirms the final size on site.

Continuous peak (24 h hold)0.8 kW
Start-up peak (cool-down after switch-on)1.7 kW
1.7 kW · 5,835 BTU/h · 1.6 kW sensible + 0.1 kW latent

Common split sizes

  • 2.0 kWBest fit
  • 2.5 kW
  • 3.5 kW
  • 5.0 kW
  • 7.0 kW

Calculated peak is below the smallest standard 2.0 kW split class; an inverter unit modulates down at part load.

Estimated summer running cost (May–Sep)

Electricity / summer111 kWh
Cost / summer€42

1,208 cooling hours · 808 kWh heat removed

Certified installation required for split units in Germany and the EU

Fixed split air conditioners are non-hermetically sealed systems charged with fluorinated greenhouse gases (F-gases, such as R32). Under EU Regulation (EU) 2024/573 (Articles 10 and 11(7)) and Germany’s ChemKlimaschutzV, they must be installed and commissioned by a certified HVAC company — DIY installation is not permitted and retailers must obtain proof of certified installation. Portable monoblock units are factory-sealed plug-in appliances.

Method and limits

Hourly single-room heat-balance method based on the simple hourly 5R1C thermal network (EN ISO 13790 Annex C), driven by static PVGIS 5.3 climate files. Not a certified calculation.

FactorApplied nowBasis & primary source
City & 1% summer design dayBerlin (DE) · 1% 30.6 °C · 30.0 °C / 37% RH @ 15:00 local time (CEST · UTC+2)Static city files from GeoNames (CC BY 4.0) and PVGIS 5.3 (PVGIS-SARAH3 / ERA5, 2005–2023): 1% exceedance design day & May–September TMY (computed in UTC internally, displayed in local time).
Walls, roof, glazing & shadingU_wall 0.49 · U_roof 0.35 · U_win 1.7 W/(m²·K) · g 0.63 · F_shade 0.60TABULA/EPISCOPE residential U-values (DE) and SEAI DEAP 4.3.1 glazing, frame (F_F = 0.7) and shading factors.
Thermal mass preset (C_m / A_m)Medium · C_m 4,125 kJ/K · A_m 62.5 m²ETH Zurich City Energy Analyst (ENVELOPE_MASS.csv, MIT) & Horvat & Dović (2016): Light 110 / Medium 165 / Heavy 300 kJ/(m²·K).
Solar geometry & sol-air5 m² (S) · α = 0.6, R_se = 0.04, F_W = 0.9Spencer (1971) / Sandia PVPMC solar position & isotropic sky irradiance (albedo 0.2); sol-air temperature (Bendjemila et al. 2026) & horizontal roof ΔR = 63 W/m² (Manyumbu et al. 2023).
People & internal gains2 × (70 W + 45 W) · 75 W (3 W/m²)Occupants: 70 W sensible + 45 W latent (IDAE); 3 W/m² baseline (TABULA); home office 153 W (CTU/TUe); TV 98 W (EU 2019/2021); cooking 1,172 W (ENERGY STAR 4,000 BTU/h).
Hourly 5R1C heat balance1,625 W + 90 W = 1,715 W (n = 0.4 h⁻¹)Method based on the simple hourly 5R1C model of EN ISO 13790 Annex C (ETH RC_BuildingSimulator) including cool-down after switch-on for part-day use & psychrometrics (Xu et al. 2026).
kW to BTU/h conversion1 kW = 3,412 BTU/hNIST Special Publication 811 (International Table BTU = 1,055.05585262 J → 3,412 BTU/h per kW).
May–September electricity & cost808 kWh ÷ SEER 7.3 (SEER 6.10–8.49) × 37.97 ct/kWhHourly May–September cooling demand (PVGIS TMY) ÷ typical SEER/EER within the EU Regulation 626/2011 & 206/2012 class range (see table below); default Germany price 37.97 ct/kWh (Destatis H1 2026).

EU energy classes and modelled SEER / EER values

Each EU energy label class defines a seasonal efficiency range in Commission Delegated Regulation (EU) No 626/2011 (Annex II). For electricity estimates, this calculator uses one typical value within each class range:

EU energy classValue usedRegulation (EU) 626/2011 rangeSelection basis
Split AC · A+++SEER 8.50SEER ≥ 8.50Typical lower bound of the open-ended class
Split AC · A++SEER 7.30SEER 6.10–8.49Typical midpoint within the class range
Split AC · A+SEER 5.85SEER 5.60–6.09Typical midpoint within the class range
Split AC · ASEER 5.35SEER 5.10–5.59Typical midpoint within the class range
Split AC · BSEER 4.85SEER 4.60–5.09Typical midpoint within the class range
Portable monoblock · AEER 2.60EER 2.60–3.09Typical class lower bound (also EU Ecodesign 206/2012 minimum)

Known limits

  • Design-day humidity limit: PVGIS multi-year seriescalc does not include relative humidity (RH). Design-day hourly RH is reconstructed from the mean water-vapor partial pressure of the city’s hottest 5% May–September TMY hours.
  • Single adiabatic room: heat flow through interior walls, floors or open doors to adjacent rooms is not modelled.
  • Representative building U-values: TABULA national averages cover 20 European countries; other European countries use the 20-country TABULA mean.
  • No micro-shading or urban heat island: neighbouring buildings, overhangs, balconies and dense city-centre night heat islands are not modelled beyond PVGIS terrain horizon.
  • Rated SEER/EER conversion: seasonal electricity divides hourly cooling demand by rated SEER or EER rather than part-load compressor curves.

Primary sources & data attributions

  1. Bosch Home Comfort · Klimaanlagen-Kühlleistung berechnen (sizing guide)www.bosch-homecomfort.com · Checked
  2. Bosch Home Comfort · Klimaanlage Wohnung (60 / 80 / 100 W/m² table & portable note)www.bosch-homecomfort.com · Checked
  3. Daikin Germany · Leitfaden zum Bemessen von Klimaanlagenwww.daikin.de · Checked
  4. ENERGY STAR · Room Air Conditioners sizing adjustmentswww.energystar.gov · Checked
  5. Commission Delegated Regulation (EU) No 626/2011 · Energy labelling of air conditionerseur-lex.europa.eu · Checked
  6. Commission Regulation (EU) No 206/2012 · Ecodesign requirements for air conditionerseur-lex.europa.eu · Checked
  7. NIST Special Publication 811, Appendix B.8 · International Table BTU conversionwww.nist.gov · Checked
  8. Destatis · Average household electricity prices in Germany (H1 2026: 37.97 ct/kWh)www.destatis.de · Checked
  9. Commission Regulation (EU) 2019/2021 · Ecodesign for electronic displays (Annex II)eur-lex.europa.eu · Checked
  10. Duška, Lukeš, Barták & Hensen (Clima 2007) · Heat gains from PCs and LCD monitorspure.tue.nl · Checked
  11. Regulation (EU) 2024/573 · Fluorinated greenhouse gases (Articles 10 and 11(7))eur-lex.europa.eu · Checked
    Article 11(7): “Non-hermetically sealed equipment charged with fluorinated greenhouse gases listed in Annex I and in Section 1 of Annex II may only be sold to an end user where evidence is provided that the installation is to be carried out by an undertaking certified in accordance with Article 10.”
  12. GeoNames · European city database (cities5000.zip, all EU/EEA/UK/CH national capitals included, CC BY 4.0)download.geonames.org · Checked
  13. PVGIS 5.3 © European Union, 2001–2026 · Non-interactive API (TMY & multi-year hourly series)joint-research-centre.ec.europa.eu · Checked
  14. TABULA / EPISCOPE Work Report · Evaluation of the TABULA Database (Table 7 U-values & Section 2 window ratios)episcope.eu · Checked
  15. TABULA Common Calculation Method · Standard residential ACH, internal gains, frame & incidence factorsepiscope.eu · Checked
  16. SEAI DEAP Guide 4.3.1 · Default U-values, g-values and frame factors for windowsdeapguide.seai.ie · Checked
  17. SEAI DEAP Guide 4.3.1 · Appendix P summer shading factors and ventilation air change ratesdeapguide.seai.ie · Checked
  18. RC_BuildingSimulator (MIT) · Open-source 5R1C hourly thermal network (method based on EN ISO 13790 Annex C)github.com · Checked
  19. ETH Zurich City Energy Analyst (MIT) · Light, medium & heavy thermal mass presets (ENVELOPE_MASS.csv)github.com · Checked
  20. Horvat & Dović (2016), Transactions of FAMENA 40 · 5R1C effective mass area & latent enthalpyhrcak.srce.hr · Checked
  21. Sandia PVPMC · Solar position, angle of incidence & isotropic plane-of-array irradiancepvpmc.sandia.gov · Checked
  22. Quan et al. (2024), ESSD 16, 961–983 · Spencer (1971) solar declination & Iqbal zenith modelessd.copernicus.org · Checked
  23. Bendjemila et al. (2026), Buildings 16(23), 4718 · Sol-air R_se = 0.04 m²·K/W, absorptance & ground albedowww.mdpi.com · Checked
  24. Manyumbu, Martin & Chiu (2023), Energies 16(14), 5391 · Horizontal roof long-wave sky radiation ΔR = 63 W/m²www.mdpi.com · Checked
  25. IDAE · Thermal wellbeing: metabolic sensible/latent heat gains & summer comfort rangewww.idae.es · Checked
  26. Xu et al. (2026), Sustainability 18(21), 11286 · Moist air saturation vapor pressure, humidity ratio & enthalpywww.mdpi.com · Checked
  27. Chemikalien-Klimaschutzverordnung (ChemKlimaschutzV) · Germany F-gas ruleswww.gesetze-im-internet.de · Checked

Related HVAC guides on Mamly

Read our manufacturer-sourced guides on capacity ratings, SEER, inverter modulation and refrigerants.